Solve ISO or insulation fault of Solar PV System
Before connecting to electricity Grid, our On-Grid solar inverters measure the insulation resistance of solar panels strings compared to ground. If the insulation resistance measured by the inverter is less than 1000 kohm, the inverter does not connect to the grid and alarms ISO fault. The causes may be:
Damaged PV panels.
Junction boxes of the panels not properly sealed, so allowing water and/or damp seepage.
Problems in the connections between panels (not perfectly connected).
Poor quality cable junctions.
Presence of unsuitable (trigger voltage lower than the characteristics of the PV generator strings) or damaged overvoltage surge arresters outside the inverter in the DC section.
Presence of damp inside the field panel (damp increases leakage and can therefore be the cause of a reduction in insulation resistance)
What's the Difference between on Grid inverter and Off Grid inverter?
Basically, inverter converts the DC (Direct Current) power source into AC (Alternating Current). On Grid or Grid Tie inverters are inverters that you can connect directly to the power outlet or Grid. Yes, your house will have two different power sources, and it will not explode. There's a micro-controller inside that synchronizes the generated power to the utility Grid. You cannot do that in regular inverter or Off Grid inverters. If you will connect the Off Grid inverter to the Grid lines, the inverter will be DAMAGED and might cause injuries and fire because it is not designed to sync the generated power to the Grid. Hybrid Off Grid Inverters also known as Grid Tie Inverters with battery backup are simply a combination of On Grid inverter and Off-Grid inverters but with MPPT solar charge controller to charge batteries.
120V-240Vac Split Phase inverter
A split-phase or single-phase three-wire system is a type of single-phase electric power distribution, only used in Americas Power Grid. It is quite different from China or Europe Grid power systems 230V-380Vac.